Downstream Encryption Key Download Will Fail if any I/O Modules Are Offline
Last Modified on 09/24/2024 11:38 am EDT
Problem Overview
Downstream Encryption Key Download Will Fail if any I/O Modules Are Offline
Detailed Description
If any Series 2 I/O modules (LNL-1300, LNL-1320, LNL-1100, LNL-1200) are offline when the Download Encryption Keys command is issued from Alarm Monitoring, the command will fail and some or all of the boards will not receive the keys. To work around this issue, ensure all boards are online or if a board is known to be offline delete it from the system to download keys to the other boards.Applies To
OnGuard 2009 (6.3.249) or laterAdditional Information