Symptom
An LNL-500, LNL-1000, or LNL-2000 Intelligent System Controller (ISC) may randomly perform a Database Download. If this occurs, the panel cycles power.
This issue only occurs when Hard Global APB is used.
This issue only occurs when Hard Global APB is used.
Resolution
There was an issue that was found in the LNL-500, LNL-1000, and LNL-2000 ISC firmware. Firmware versions 3.121 and above resolve this issue.
Applies To
OnGuard (All versions)
Additional Information
This issue does not apply to an LNL-2220, LNL-3300, or LNL-2210 ISC.